performing-power-grid-cybersecurity-assessment
This skill covers conducting cybersecurity assessments of electric power grid infrastructure including generation facilities, transmission substations, distribution systems, and energy management system (EMS) control centers. It addresses NERC CIP compliance verification, substation automation security, IEC 61850 protocol analysis, synchrophasor (PMU) network security, and the unique threat landscape targeting power grid operations as demonstrated by Industroyer/CrashOverride and related attacks.
What this skill does
# Performing Power Grid Cybersecurity Assessment
## When to Use
- When conducting periodic cybersecurity assessments of power grid facilities per NERC CIP requirements
- When assessing substation automation systems using IEC 61850 GOOSE and MMS protocols
- When evaluating the security of an Energy Management System (EMS) or SCADA control center
- When assessing synchrophasor (PMU) networks and wide-area monitoring systems
- When preparing for regional entity compliance audits or internal security reviews
**Do not use** for non-BES systems below NERC registration thresholds, for general OT assessment without power grid specifics (see performing-ot-network-security-assessment), or for physical security assessment of generation facilities without cyber scope.
## Prerequisites
- Understanding of electric power grid architecture (generation, transmission, distribution)
- Familiarity with NERC CIP standards and BES Cyber System categorization
- Knowledge of power grid protocols (IEC 61850, IEC 60870-5-104, DNP3, ICCP/TASE.2)
- Passive monitoring tools for substation network traffic analysis
- Access to EMS/SCADA architecture documentation and network diagrams
## Workflow
### Step 1: Map Power Grid Cyber Architecture
Identify and document all cyber systems supporting grid operations including EMS, SCADA, substation automation, and communication infrastructure.
```yaml
# Power Grid Cyber Architecture Assessment
facility_type: "Regional Transmission Organization Control Center"
ems_systems:
primary_ems:
vendor: "GE Grid Solutions"
product: "EMS/SCADA (formerly XA/21)"
functions:
- "State estimation"
- "Automatic generation control (AGC)"
- "Security-constrained economic dispatch"
- "Contingency analysis"
protocols:
- "ICCP/TASE.2 (inter-control center)"
- "DNP3 (substation RTU polling)"
- "IEC 60870-5-104 (substation polling)"
backup_control_center:
location: "Geographically diverse backup site"
sync_method: "Real-time database mirroring"
switchover_time: "< 5 minutes"
substation_automation:
count: 145
system_types:
- vendor: "ABB"
product: "RTU560"
protocol: "DNP3 over TCP/IP"
count: 85
- vendor: "SEL"
product: "SEL-3530 RTAC"
protocol: "IEC 61850 MMS + GOOSE"
count: 40
- vendor: "Siemens"
product: "SICAM A8000"
protocol: "IEC 60870-5-104"
count: 20
communications:
primary: "MPLS WAN (carrier-provided)"
backup: "Licensed microwave radio"
last_mile: "Fiber optic to substation"
synchrophasor_network:
pmu_count: 75
pdc: "GE PDC (Phasor Data Concentrator)"
communication: "IEEE C37.118.2 over dedicated network"
data_rate: "30-60 samples per second"
```
### Step 2: Assess Substation Automation Security
Evaluate IEC 61850-based substation automation for protocol security, access controls, and network segmentation.
```python
#!/usr/bin/env python3
"""Power Grid Substation Security Assessor.
Evaluates security of IEC 61850-based substation automation
systems including GOOSE messaging, MMS client/server, and
network architecture.
"""
import json
import sys
from dataclasses import dataclass, field, asdict
from datetime import datetime
@dataclass
class SubstationFinding:
finding_id: str
severity: str
category: str
title: str
description: str
affected_systems: list
nerc_cip_ref: str
iec_62351_ref: str
remediation: str
class SubstationAssessment:
"""Assesses cybersecurity of substation automation systems."""
def __init__(self, substation_name):
self.name = substation_name
self.findings = []
self.counter = 1
def assess_iec61850_security(self, config):
"""Assess IEC 61850 protocol security."""
# GOOSE message authentication
if not config.get("goose_authentication"):
self.findings.append(SubstationFinding(
finding_id=f"SUB-{self.counter:03d}",
severity="critical",
category="Protocol Security",
title="IEC 61850 GOOSE Messages Lack Authentication",
description=(
"GOOSE messages used for protection signaling between IEDs "
"are not authenticated. An attacker on the station bus could "
"inject false trip/close commands to circuit breakers."
),
affected_systems=config.get("goose_publishers", []),
nerc_cip_ref="CIP-005-7 R1.5 - ESP internal communications",
iec_62351_ref="IEC 62351-6 - GOOSE/SV authentication",
remediation=(
"Implement IEC 62351-6 GOOSE authentication using digital "
"signatures. Deploy VLAN isolation for GOOSE traffic as interim."
),
))
self.counter += 1
# MMS service access control
if not config.get("mms_authentication"):
self.findings.append(SubstationFinding(
finding_id=f"SUB-{self.counter:03d}",
severity="high",
category="Protocol Security",
title="MMS Client Connections Lack Authentication",
description=(
"MMS (Manufacturing Message Specification) connections to IEDs "
"do not require client authentication. Any device on the station "
"bus can read/write IED configuration and operate breakers."
),
affected_systems=config.get("mms_servers", []),
nerc_cip_ref="CIP-007-6 R5 - System Access Controls",
iec_62351_ref="IEC 62351-4 - MMS security profiles",
remediation="Enable TLS for MMS connections per IEC 62351-4.",
))
self.counter += 1
# Station bus segmentation
if not config.get("station_bus_segmented"):
self.findings.append(SubstationFinding(
finding_id=f"SUB-{self.counter:03d}",
severity="high",
category="Network Architecture",
title="Flat Station Bus Network Without Segmentation",
description=(
"Station bus connects all IEDs, HMI, engineering access, "
"and WAN gateway on a single VLAN without segmentation."
),
affected_systems=["All station bus devices"],
nerc_cip_ref="CIP-005-7 R1 - ESP boundary",
iec_62351_ref="IEC 62351-10 - Security architecture",
remediation=(
"Segment station bus into VLANs: protection IEDs, "
"measurement IEDs, station HMI, and WAN gateway."
),
))
self.counter += 1
def assess_remote_access(self, config):
"""Assess remote access security for substations."""
if config.get("direct_vendor_access"):
self.findings.append(SubstationFinding(
finding_id=f"SUB-{self.counter:03d}",
severity="critical",
category="Remote Access",
title="Direct Vendor Remote Access to Substation Without MFA",
description=(
"Vendor support has direct VPN access to substation network "
"without traversing an intermediate system or requiring MFA."
),
affected_systems=["Substation WAN gateway"],
nerc_cip_ref="CIP-005-7 R2 - Remote Access Management",
iec_62351_ref="IEC 62351-8 - Role-based access control",
remediation=(
"Route vendor access through corporate jump server with MFA. "
"Implement session recording per CIP-005-7 R2.4."
),
))
self.counter += 1
def generate_report(self):
"""GeRelated in Security
mac-ops
IncludedComprehensive macOS workstation operations — diagnose kernel panics, identify failing drives, audit launchd startup items, decode wake reasons, triage TCC permission denials, manage APFS snapshots, recover from no-boot. Use for: Mac is slow, slow bootup, won't boot, kernel panic, kernel_task hot, mds_stores CPU, photoanalysisd, cloudd, login loop, gray screen, sleep wake failure, drive failing, IO errors, APFS snapshots eating space, Time Machine local snapshots, Spotlight indexing, launchd, LaunchAgent, LaunchDaemon, login items, TCC permissions, Full Disk Access, Screen Recording denied, Gatekeeper, quarantine, com.apple.quarantine, app is damaged, helper tool, /Library/PrivilegedHelperTools, pmset, wake reasons, dark wake, sysdiagnose, panic.ips, DiagnosticReports, configuration profile, MDM profile, remote diagnostics over SSH.
a11y-audit
IncludedRun accessibility audits on web projects combining automated scanning (axe-core, Lighthouse) with WCAG 2.1 AA compliance mapping, manual check guidance, and structured reporting. Output is configurable: markdown report only, markdown plus machine-readable JSON, or markdown plus issue tracker integration. Use this skill whenever the user mentions "accessibility audit", "a11y audit", "WCAG audit", "accessibility check", "compliance scan", or asks to check a web project for accessibility issues. Also trigger when the user wants to verify WCAG conformance or map findings to a specific standard (CAN-ASC-6.2, EN 301 549, ADA/AODA).
erpclaw
IncludedAI-native ERP system with self-extending OS. Full accounting, invoicing, inventory, purchasing, tax, billing, HR, payroll, advanced accounting (ASC 606/842, intercompany, consolidation), and financial reporting. 413 actions across 14 domains, 43 expansion modules. Constitutional guardrails, adversarial audit, schema migration. Double-entry GL, immutable audit trail, US GAAP.
assess
IncludedAssesses and rates quality 0-10 across multiple dimensions (correctness, maintainability, security, performance, testability, simplicity) with pros/cons analysis. Compares against project conventions and prior decisions from memory. Produces structured evaluation reports with actionable improvement suggestions. Use when evaluating code, designs, architectures, or comparing alternative approaches.
spring-boot-security-jwt
IncludedProvides JWT authentication and authorization patterns for Spring Boot 3.5.x covering token generation with JJWT, Bearer/cookie authentication, database/OAuth2 integration, and RBAC/permission-based access control using Spring Security 6.x. Use when implementing authentication or authorization in Spring Boot applications.
code-hardcode-audit